Pegler Yorkshire Logo

Ductile iron Y type strainer. PN16, -10°C to 120°C 13 bar at 220°C

V912 Strainer

Ductile iron Y type strainer. PN16, -10°C to 120°C 13 bar at 220°C
SizePattern No.Pack 1 QtyPack 2 QtyCodeBarcodePrice (£) each ex VAT
DN65V912105022050555564£268.82
DN80V912105022050555571£325.14
DN100V912105022050555588£466.38
DN125V912105022050555595£863.76
DN150V912105022050555601£1119.45
DN200V912105022050555618£1693.59
DN250V912105022050555625£2755.80
DN300V912105022050555632£4054.74

V912 Strainer

Ductile iron Y type strainer. PN16, -10°C to 120°C 13 bar at 220°C dimensions
CodeDescriptionABCD
15361DN65 V91229018512218014.30
15362DN80 V91231020013821518.0
15363DN100 V91235022015823525.0
15364DN125 V91240025018827540.0
15365DN150 V91248028521230554.0
15366DN200 V912600340268390108.0
15367DN250 V912730405320540180.0
15368DN300 V912850455378680330.0
Pegler Yorkshire reserve the right to change specifications
SizePattern No.CodeKv m3/h
DN65V9121536193.00
DN80V91215362136.00
DN100V91215363229.00
DN125V91215364363.00
DN150V91215365499.00
DN200V91215366817.00
DN250V912153671361.00
DN300V912153681928.00
Pegler Yorkshire reserve the right to change specifications

Pegler 5 Year Guarantee - Terms and Conditions

Products are subject to a 5 year guarantee that is between Pegler and the final purchaser of the product.

The guarantee is subject to proof of purchase being supplied.

This guarantee does not affect any statutory rights the consumer may have in law.

The guarantee covers manufacturing or material defects when installed in accordance with our instructions on specified tube materials and applications, and does not cover parts subject to normal wear and tear.

This product range has been designed for the use of homeowners, domestic and commercial applications and therefore the Guarantee is subject to the product being properly selected for their intended service conditions.

The guarantee is not applicable where the product is fitted contrary to the conditions in the fitting instructions.

This is reinforced where valves are covered by the European Pressure Equipment Directive (PED97/23/EC) where Installation, Operating and Maintenance Instructions are supplied with each product and/or carton.

Provided it is installed correctly and receives adequate preventative maintenance it should give years of trouble–free service.

Abusive behaviour and accidental damage to the product are not covered by this guarantee.

The extent of this liability is limited to the cost of the replacement of the defective item and not to installation or consequential damages.

ComponentMaterial
BodyDuctile iron
CapDuctile iron
CoverDuctile iron
StrainerStainless steel
SealFibre TesnitBA-U
ScreenStainless steel
GasketTeflon/Graphite
PlugBrass
SizePattern No.CodeMesh Diameter
DN50V91215360 
DN65V912153611.5mm
DN80V912153621.5mm
DN100V912153633.0mm
DN125V912153643.0mm
DN150V912153653.0mm
DN200V912153663.0mm
DN250V912153673.0mm
DN300V912153683.0mm
Pegler Yorkshire reserve the right to change specifications
SizeCodeFlange Diameter (mm)Pitch Circle Diameter (mm)No of BoltsBolt Diameter (mm)Hole Diameter (mm)Raised Face Diameter (mm)Raised Face Height (mm)Thickness of Flange (mm)
DN5015360--------
DN65153611851454 (2)M1619--20
DN80153622001608M1619--22
DN100153632201808M1619--24
DN125153642502108M1619--26
DN150153652852408M2023--26
DN2001536634029512M2023--30
DN25015367405 (2)35512M2428--32
DN30015368460 (2)41012M2428--32
Pegler Yorkshire reserve the right to change specifications
SteamWaterOilAirGas InertGas Combustible†Gas Corrosive††Gas Oxygen
noyesnononononono
Pegler Yorkshire reserve the right to change specifications

Gas application guide
Class 1. INERT Air, argon, carbon dioxide, helium, nitrogen
Class 2. COMBUSTIBLE Hydrogen, methane, natural gas, town gas
Class 3. CORROSIVE Chlorine, sulphur dioxide Class 4. OXYGEN
Class 1. INERT Air, argon, carbon dioxide, helium, nitrogen
† Valves are suitable for British Gas Applications Family Gases 1, 2 and 3.
†† Suitable in applications where moisture is completely absent.